Roger M.

Roger M. Job Checkin

Responded to no-heat call for 15-year-old furnace system. Diagnosed faulty gas valve that was receiving proper signal but not opening, causing pilot light failure. Due to component failure and system age, replaced entire furnace unit rather than just the valve. Documented significant corrosion and wear on internal components through inspection photos.

Responded to no-heat call for 15-year-old furnace system. Diagnosed faulty gas valve that was receiving proper signal but not opening, causing pilot light failure. Due to component failure and system age, replaced entire furnace unit rather than just the valve. Documented significant corrosion and wear on internal components through inspection photos. Responded to no-heat call for 15-year-old furnace system. Diagnosed faulty gas valve that was receiving proper signal but not opening, causing pilot light failure. Due to component failure and system age, replaced entire furnace unit rather than just the valve. Documented significant corrosion and wear on internal components through inspection photos.

Craig M.

Craig M. Job Checkin

Responded to a no-heat call where furnace was repeatedly entering standby mode requiring manual reset. Diagnosed error codes indicating "flame present when shouldn't be." Replaced control board and switches to resolve the recurring issue that had persisted since our previous service visit one week prior.

Responded to a no-heat call where furnace was repeatedly entering standby mode requiring manual reset. Diagnosed error codes indicating "flame present when shouldn't be." Replaced control board and switches to resolve the recurring issue that had persisted since our previous service visit one week prior. Responded to a no-heat call where furnace was repeatedly entering standby mode requiring manual reset. Diagnosed error codes indicating "flame present when shouldn't be." Replaced control board and switches to resolve the recurring issue that had persisted since our previous service visit one week prior.

Craig M.

Craig M. Job Checkin

Responded to no heat complaint on 9-year-old Amana furnace with intermittent ignition failure occurring primarily at night. Diagnostic testing revealed stored error code 7 (ignition lockout) in system history, but all components functioned properly during inspection. Performed electrical testing on ignition system components with no faults detected. Will continue to monitor situation as intermittent issue could not be replicated during service call.

Responded to no heat complaint on 9-year-old Amana furnace with intermittent ignition failure occurring primarily at night. Diagnostic testing revealed stored error code 7 (ignition lockout) in system history, but all components functioned properly during inspection. Performed electrical testing on ignition system components with no faults detected. Will continue to monitor situation as intermittent issue could not be replicated during service call. Responded to no heat complaint on 9-year-old Amana furnace with intermittent ignition failure occurring primarily at night. Diagnostic testing revealed stored error code 7 (ignition lockout) in system history, but all components functioned properly during inspection. Performed electrical testing on ignition system components with no faults detected. Will continue to monitor situation as intermittent issue could not be replicated during service call.

Jon W

Jon W Job Checkin

Diagnosed 20-year-old furnace with intermittent operation and cool air output. Upon inspection, identified multiple critical failures including pressure switch, high limit control, and compromised secondary heat exchanger. Due to extent of component failures and unit age, complete furnace replacement was recommended and performed.

Diagnosed 20-year-old furnace with intermittent operation and cool air output. Upon inspection, identified multiple critical failures including pressure switch, high limit control, and compromised secondary heat exchanger. Due to extent of component failures and unit age, complete furnace replacement was recommended and performed. Diagnosed 20-year-old furnace with intermittent operation and cool air output. Upon inspection, identified multiple critical failures including pressure switch, high limit control, and compromised secondary heat exchanger. Due to extent of component failures and unit age, complete furnace replacement was recommended and performed.

Roger M.

Roger M. Job Checkin

Responded to no-heat call on aging Goodman furnace that was previously serviced for a leak. Diagnosed issue with sticking door switch that was preventing proper operation. Restored normal functionality by adjusting the door switch mechanism. Performed combustion analysis with Testo 310 II, confirming system is now operating within acceptable parameters (CO: 21ppm, efficiency: 67.2%).

Responded to no-heat call on aging Goodman furnace that was previously serviced for a leak. Diagnosed issue with sticking door switch that was preventing proper operation. Restored normal functionality by adjusting the door switch mechanism. Performed combustion analysis with Testo 310 II, confirming system is now operating within acceptable parameters (CO: 21ppm, efficiency: 67.2%). Responded to no-heat call on aging Goodman furnace that was previously serviced for a leak. Diagnosed issue with sticking door switch that was preventing proper operation. Restored normal functionality by adjusting the door switch mechanism. Performed combustion analysis with Testo 310 II, confirming system is now operating within acceptable parameters (CO: 21ppm, efficiency: 67.2%).

Roger M.

Roger M. Job Checkin

Responded to service call for water leakage from HVAC system. Diagnosed failed condensation pump as root cause of the issue. Removed defective pump and installed new replacement unit, restoring proper condensate drainage and resolving the water leak problem.

Responded to service call for water leakage from HVAC system. Diagnosed failed condensation pump as root cause of the issue. Removed defective pump and installed new replacement unit, restoring proper condensate drainage and resolving the water leak problem. Responded to service call for water leakage from HVAC system. Diagnosed failed condensation pump as root cause of the issue. Removed defective pump and installed new replacement unit, restoring proper condensate drainage and resolving the water leak problem.

Charles P.

Charles P. Job Checkin

Diagnosed customer-reported leak from spout and installed customer-supplied tub shower valve, spout, and head assembly. Completed installation through existing access panel behind valve. No warranty provided on customer-supplied parts as per company policy.

Diagnosed customer-reported leak from spout and installed customer-supplied tub shower valve, spout, and head assembly. Completed installation through existing access panel behind valve. No warranty provided on customer-supplied parts as per company policy. Diagnosed customer-reported leak from spout and installed customer-supplied tub shower valve, spout, and head assembly. Completed installation through existing access panel behind valve. No warranty provided on customer-supplied parts as per company policy.

Charles P.

Charles P. Job Checkin

Successfully installed customer-supplied tub shower valve, spout, and shower head through existing wall access. Work included mounting brass mixing valve assembly on wooden support with proper copper pipe connections. No warranty provided on customer-supplied parts as per company policy.

Successfully installed customer-supplied tub shower valve, spout, and shower head through existing wall access. Work included mounting brass mixing valve assembly on wooden support with proper copper pipe connections. No warranty provided on customer-supplied parts as per company policy. Successfully installed customer-supplied tub shower valve, spout, and shower head through existing wall access. Work included mounting brass mixing valve assembly on wooden support with proper copper pipe connections. No warranty provided on customer-supplied parts as per company policy.

Jeff F.

Jeff F. Job Checkin

Completed installation of a 70K BTU 80% efficient furnace with chimney liner. Installed condensate drain pan for future coil addition. Ductwork inspection revealed significant dust accumulation in the existing system, which was documented with photos.

Completed installation of a 70K BTU 80% efficient furnace with chimney liner. Installed condensate drain pan for future coil addition. Ductwork inspection revealed significant dust accumulation in the existing system, which was documented with photos. Completed installation of a 70K BTU 80% efficient furnace with chimney liner. Installed condensate drain pan for future coil addition. Ductwork inspection revealed significant dust accumulation in the existing system, which was documented with photos.

Craig M.

Craig M. Job Checkin

Responded to no-heat service call for aging furnace system. Upon inspection, discovered severely cracked heat exchanger and seized blower motor rod that prevented successful motor replacement. Provided customer with replacement options and scheduled follow-up sales consultation to discuss system replacement recommendations due to safety concerns.

Responded to no-heat service call for aging furnace system. Upon inspection, discovered severely cracked heat exchanger and seized blower motor rod that prevented successful motor replacement. Provided customer with replacement options and scheduled follow-up sales consultation to discuss system replacement recommendations due to safety concerns. Responded to no-heat service call for aging furnace system. Upon inspection, discovered severely cracked heat exchanger and seized blower motor rod that prevented successful motor replacement. Provided customer with replacement options and scheduled follow-up sales consultation to discuss system replacement recommendations due to safety concerns.

Koshoua V.

Koshoua V. Job Checkin

Performed routine maintenance on 10-year-old furnace showing signs of corrosion and rust buildup. Cleared condensation trap to address water leaking from ceiling pipes, removed accumulated dust and debris, and replaced filters with instruction to homeowner on future maintenance. Control board appears operational with proper wiring connections intact.

Performed routine maintenance on 10-year-old furnace showing signs of corrosion and rust buildup. Cleared condensation trap to address water leaking from ceiling pipes, removed accumulated dust and debris, and replaced filters with instruction to homeowner on future maintenance. Control board appears operational with proper wiring connections intact. Performed routine maintenance on 10-year-old furnace showing signs of corrosion and rust buildup. Cleared condensation trap to address water leaking from ceiling pipes, removed accumulated dust and debris, and replaced filters with instruction to homeowner on future maintenance. Control board appears operational with proper wiring connections intact.

Roger M.

Roger M. Job Checkin

Performed maintenance inspection on 12-44 year old American Standard natural gas furnace. Identified critical safety issue: cracked heat exchanger. Completed replacement of either the full unit or heat exchanger component. Verified proper thermostat operation and installed clean air filter.

Performed maintenance inspection on 12-44 year old American Standard natural gas furnace. Identified critical safety issue: cracked heat exchanger. Completed replacement of either the full unit or heat exchanger component. Verified proper thermostat operation and installed clean air filter. Performed maintenance inspection on 12-44 year old American Standard natural gas furnace. Identified critical safety issue: cracked heat exchanger. Completed replacement of either the full unit or heat exchanger component. Verified proper thermostat operation and installed clean air filter.

Jared R.

Jared R. Job Checkin

Conducted re-inspection with White Bear Township officials for generator installation, which received final approval. Completed system setup including purging gas lines, configuring settings, setting system to auto mode, and verifying proper operation of generator and garage heater. Documentation includes photos of gas line connections and pressure gauge reading approximately 50-60 PSI.

Conducted re-inspection with White Bear Township officials for generator installation, which received final approval. Completed system setup including purging gas lines, configuring settings, setting system to auto mode, and verifying proper operation of generator and garage heater. Documentation includes photos of gas line connections and pressure gauge reading approximately 50-60 PSI. Conducted re-inspection with White Bear Township officials for generator installation, which received final approval. Completed system setup including purging gas lines, configuring settings, setting system to auto mode, and verifying proper operation of generator and garage heater. Documentation includes photos of gas line connections and pressure gauge reading approximately 50-60 PSI.

Jared R.

Jared R. Job Checkin

Responded to a generator gas line issue where customer reported zero pressure. Located and repaired a small leak at the union connection. System pressurized to required 30psi and verified leak-free operation.

Responded to a generator gas line issue where customer reported zero pressure. Located and repaired a small leak at the union connection. System pressurized to required 30psi and verified leak-free operation. Responded to a generator gas line issue where customer reported zero pressure. Located and repaired a small leak at the union connection. System pressurized to required 30psi and verified leak-free operation.

Tim M.

Tim M. Job Checkin

Responded to service call for toilet leaking from base. Diagnosed failed wax ring seal. Properly shut off water supply, disconnected toilet, removed old wax ring, and installed new wax ring seal. Reset toilet with proper alignment, reconnected water supply line, and tested for proper function and absence of leaks.

Responded to service call for toilet leaking from base. Diagnosed failed wax ring seal. Properly shut off water supply, disconnected toilet, removed old wax ring, and installed new wax ring seal. Reset toilet with proper alignment, reconnected water supply line, and tested for proper function and absence of leaks. Responded to service call for toilet leaking from base. Diagnosed failed wax ring seal. Properly shut off water supply, disconnected toilet, removed old wax ring, and installed new wax ring seal. Reset toilet with proper alignment, reconnected water supply line, and tested for proper function and absence of leaks.